Variable Speed Drive Triol AK06 Line PS

Variable Speed Drive AK06 line PS is another complete solution for the efficient control of installations with both induction and permanent magnet motors, as well as for fulfilling the requirements of IEEE519 standard.

PS line drives have an integrated phase-shifting autotransformer, which, in combination with 24-pulse rectifier, provides 5% level of harmonic distortion to the input network in the load range from 25% to 100% in accordance with the IEEE 519 standard, and allows operation at frequency supply deviation ±5%.

Distinctive benefits of Variable Speed Drive Triol AK06:

  • Maximization of Production
  • Commissioning is a snap
  • Cost-Saving
  • Investment Savings
  • ESP run life extensions
  • Operating temperature range: -20 °С … +60 °С
  • Enclosure: NEMA4, NEMA4X
  • PSA (phase shifting autotransformer)
ParameterValue
Power supply, V
  • 3×380 ± 15% / 3×480 (-15% … + 10%)
  • 50% continuously with reduced output power
  • 65% up to 500 ms (with a decrease of output power)
Input Frequency, Hz50±1 Hz and/or 60±1 Hz
Rated output current, A100 – 2000
Overcurrent characteristics120% of rated value for 60 sec
Change of frequency task increment0,1 Hz
Efficiency96 %
Passive filter efficiency>98 %
Level of current distortion in the input network THDi,%<5% in the load range from 25%* to 100%   * operation in the extended load range is optional when specified in the order
DC bus chokeBuilt-in
Sine filterBuilt-in
Capacitor unit (for voltage sags)Option, outdoor

 

Braking IGBTOption, built-in
Braking resistorOption, outdoor
Electric meterOption, built-in
GPRS routerOption, built-in
PID modeYES
HMI
  • UMKA03 controller with a 7-inch monochrome screen, push-button control
  • UMKA07 controller with LCD-TFT 7 inch display, push-button control (touch screen optional)
  • Integration of third-party controller
Output frequency
  • 1.5 – 80 Hz, in induction motor control mode
  • 1.5 – 200 Hz, in permanent magnet motor control mode
  • 1.5 – 600 Hz, in high-speed PMM control mode

 

PWM frequencyup to 8 kHz depending on VSD type
Speed maintenance accuracy (static) +/- 10% of rated speed in open-loop system
Control type
  • vector control in an open-loop system without speed feedback (for PMM)
  • scalar control: based on the characteristic voltage / frequency U / F (for induction motors)

 

Light alarm“Work”, “Waiting”, “Stop”
Operator Control VoltageOption:

  • 10 V DC, +/- 2% current not more than 30 mA
  • 24 V, 300 mA
  • 110/220 V, 10A for connecting of third-party consumers
Number of AI2 by default, optional extension +8
AI typeprogrammable 4..20 mA, 0..5 mA, 0..10 V (frequency reference / multifunction analog input)
Number of DIN2 by default, optional extension +4 or more
DIN type24 V, input resistance: 4 kOhm
Number of analog outputsOption, 4 or more programmable 4..20 mA, 0..5 mA, 0..10 V
Number of Relay OutputsOption, 8
Acceleration and deceleration rates
  • linear, from 0.1 Hz/s
  • program mode with adjustable time of reaching given frequency
InsulationGalvanic isolation between power and user circuits
Insulation resistance> 5 MOhm
Protection type
  • Overcurrent protection
  • Power switched temperature (IGBT)
  • Max. and min. voltage in the DC link
Communication portModbus
Physical interface
  • 2-wire RS-485/232 for Modbus by default
  • Ethernet (optional) – for communication with ACS /automated control system/
  • wire RS-485/232 for Modbus – for communication with a surface downhole measuring system
Frame TransmissionModbus RTU
up to 115200 bps
Enclosure protectionNEMA4, NEMA4X
Material of enclosurecarbon steel, stainless steel
Operating temperature-20°С … +60°С (-60°С optional)
Relative humidity100 %
Cooling typeAir forced