Triol AT27 Robust Xform
Place an order
Distinctive benefits
A built-in climate control
Ventilation, heating, air conditioning systems
Cold and hot air mixing chambers
Rain and snow protection
Resistance to ice
About product
Versatile and reliable solution
Medium Voltage Variable Frequency Drive AT27 line RX is a versatile and reliable solution for general industrial applications. AT27 RX is a block-box (insulated container) for outdoor use. The power cells and transformer are designed for long-term and reliable operation in harsh climatic conditions.
Factory warranty
All switching devices and output filters are installed directly in the block-box Variable Frequency Drive Triol AT27 VFD line RX. Factory warranty for the entire product. There is no division of responsibility between the manufacturer of the building and the manufacturer of the frequency converter of the standard cabinet design. Triol AT27 VFD line RX is an assurance in the reliable operation of VFD.
Installation options
Various installation options for Variable Frequency Drive Triol AT27 RX are possible: on a pile field, on a foundation, on concrete slabs.
Custom design
Triol AT27 VFD line RX custom design allows you: to take into account the features of the installation place; to design the appearance of special requirement; to equip the drive with stairs and platforms for servicing the most convenient configuration.
External warning devices
Variable Frequency Drive Triol AT27 line RX is equipped with external warning devices (alarm lamp and buzzer) that allows you monitoring the status of the drive from a distance.
Fire alarm system
Triol AT27 VFD line RX is equipped with a fire alarm system. It is optionally possible to install a burglar alarm system with access via magnetic cards and an automatic aerosol fire extinguishing system.
Features
- Operating temperature maximum range -60 ºС…+50 ºС
- Outdoor
- Enclosure NEMA3 (IP43)
- Minimum constructing and installation costs
- No expenses for HVAC system
- Color touchpad 7”
- Wi-Fi Wizard
- Induction and permanent magnet motor
- Output voltage and current sinusoidal
- High power factor ≥ 0.96
- Operating in unstable mains
- Build-in switching devices and output filters
- Full factory readiness
- Factory warranty
Specifications
Input | ||
Input voltage, kV |
3; 3.3; 4.16; 6; 6.3; 6.6; 10; 11 (-15 % ...+10 %) -45% continuous with power limit -100% not less than 100 ms with controlled generator mode of the motor |
|
Input frequency, Hz | 50 / 60 (-10 %...+10 %) | |
Power, kW |
3 / 3.3 kV 4.16 kV 6 / 6.3 / 6.6 kV 10 / 11 kV |
from 160 kW up to 3000 kW from 160 kW up to 3500 kW from 200 kW up to 5000 kW from 320 kW up to 8000 kW |
Power factor | 0.96 | |
THDi (input current), % | < 5 | |
Pulses of rectifier |
18; 24; 30; 36; 48; 54 (depends on the number of cells in each phase) |
|
Overvoltage protection | Surge arresters | |
Output | ||
Rated output voltage, kV | 3.3; 4.16, 6; 6.6; 10; 11 | |
Output frequency, Hz | from 0.5 up to 120 | |
Frequency resolution, Hz | 0.01 | |
Output current, A | 25…600 | |
Overcurrent characteristics |
120 % of rated value for 120 sec 150 % of rated value for 3 sec |
|
THDi (output current), % | < 2 | |
THDu (output voltage), % | < 5 | |
dV/dt value | < 1000 V/μs | |
Efficiency, % | ≥ 97 |
Options
Options | Description |
Copper transformer | Copper bus is the material used for transformer windings. Transformer parameters and efficiency are commensurable with the basic type of transformer with windings of aluminum busbars |
Mechanical bypass of power cells | Bypass of each power cell of the drive is made on the basis of a vacuum chamber, with a response time of not more than 4 msec |
IGBT bypass of power cells | Bypass of each power cell of the drive, made on the basis of IGBT transistors |
Additional power cell in each phase | For compensating voltage drop on the output sine-filter or reactors (if available) and the long cable line, as well as to ensure operation in the nominal mode in the case of bypassing the cells (with this option) |
Increased operating temperature | Maximum operating temperature up to +50 °С |
Side cable entry | Organization of terminals for entry power and signal cables on side of the AT27 |
Additional PCB coverage | Coating of printed circuit boards with a special varnish to protect against aggressive impurities in the air |
Electromagnetic door lock | Electromagnetic locks on the doors of the AT27 power compartments provide protection against opening doors when medium voltage is applied |
Reactors for transfer of the motor to mains | Designed to provide synchronous and shockless transfer of the motor to mains. |
Sine-filter | Designed to improve of the output current and voltage THD, as well as reduce the value of the parameter dV/dt. |
Medium-voltage switch compartment | Allow you to implement the required one-line diagram |
Profibus communication protocol | Convertor Modbus-Profibus |
Burglar alarm system | Alerts the operator of unauthorized entry into the block-box |
Automatic aerosol fire extinguishing system | Carries out automatic fire extinguishing in case of its occurrence in block-box |